Eskom Energy Emergency Preparedness - Tjaart van der Walt National Operations

Page created by Jason Bush
 
CONTINUE READING
Eskom Energy Emergency Preparedness
    Tjaart van der Walt
    National Operations
LONG TERM CAPACITY SHORTAGES

    • Eskom may face the possibility of generation inadequacy
    • It is preferable to shed load in an emergency on the IPS for a
      short period rather than risk system security by operating for
      extended periods with low frequency and voltage
    • Any operation at low frequency causes a slowing down or
      electrically driven plant auxiliaries and may make it impossible
      to increase or even maintain station generation
    • All requests for load reductions/restoration are co-ordinated
      through the Distribution NMCs by National Control
    • This presentation highlights actions when such emergencies do
      occur and does not show Eskom’s mitigation plans for such
      emergencies not to occur

                                   2
DAILY GENERATION CAPACITY AND RESERVES

    • Objective of daily operation
       – Operate generation capacity as to deliver reasonable protection
         against:
          y load forecasting errors
          y equipment failures
       – Ensure adequate regulation of frequency and power flows on
         transmission lines

    • Interruptible load is a generation reserve
       – Not part of the load shedding quota of the under-frequency load
         shedding schemes
       – Where possible, interruptible load should be used before UFLS and
         manual load reduction
    • Guidelines for the amount of spinning and operating reserves
      required on the IPS are contained in Procedure OP16 and OP17

                                      3
SYSTEM CONTROL STRUCTURE

                               765 - 220 kV System Control
                     NC

                    TOC           132 - 66 kV Operating Control
                 Dx Controls
                                        66 -11 kV
             Reticulation Controls

            Power Station Controls P.S. Auxiliaries

                           4
CONTROL CENTRES

                                 TOC
                                132 kV
                    NMC                   NMC
                   Witbank               Central
                    66 kV                 66 kV

          Bloemfontein                             Mkondeni
             132 kV               NC                132 kV
                                765 kV

                                                              Legend:
                                                                System Control
                    Bellville            Sunilaws
                    132 kV                132 kV                 TOC
                                                                 Dx Control
                                                                 Both

                                   5
RESPONSIBILITIES DURING EMERGENCIES

    • NATIONAL CONTROL CENTRE
       – Ultimate authority over and responsibility for operating the
         Eskom IPS
       – Advance Warning of Capacity Defects
          y National Control shall give notice of a future generation deficit
            by issuing the appropriate warning instruction, depending on the
            severity of the emergency
          y The warning will be issued to Distribution NMCs, directly or via
            Distribution NMCs to the Power Station Control Rooms, SAPP
            members and customers

                                    6
RESPONSIBILITIES DURING EMERGENCIES cont.

    • DISTRIBUTION CONTROL CENTRES
       – Load curtailment and/or load shedding after instructions by
         National Control
       – Restoration of load after instruction from NC
       – Switching, generation dispatch and voltage control in the
         event of a complete breakdown of all avenues of
         communication with NC
       – NOT Municipal generation assistance as this is requested by
         NC
       – NOT DMP requests as this is the function of NC

                                  7
COMMUNICATION

    • Control to Control
      – Warnings
      – System/DMP changes
      – Instructions

    • Back office to Back office
      – Other information

    • Communications department to consumer

                             8
FREQUENCY DECAY

    • Rapid freq. decline
      –Mainly due to incidents
      –Generation reserves utilised
      –Human action too slow
      –Automatic emergency schemes utilised
    • Gradual freq. decline
      –Mainly due to load pickup
      –Generation reserves utilised
      –Controller action adequate
      –Manual emergency schemes utilised

                           9
SHORT TERM CAPACITY SHORTAGE

    • Emergency Resource Merit Order (ERMO)
       – Utilised to compensate for the shortage of generation
       – The order in which the resources shall be utilised is also given in the ERMO
       – The order of resources in this Memorandum is based on the energy bid
         price (average over the past month) in increasing price order
       – Once a resource is used it is moved to the bottom of the list (for one month)
         so that the same resource is not used too often
       – Gas turbines are normally included after interruptible load

    • Emergency resources may also be called upon for transmission related
      emergencies such as incipient voltage collapse or line overloads.
    • The ERMO includes various resources to be utilised in a specific order
      to recover the frequency to 50 Hz.

                                        10
Merit Order for Managing Energy Shortages
               R equirem ents                                        S ource of C apacity                              C riteria for U tilization
                                      Em ergency reserves: at least to cover loss of largest pow er station (3600M W )
                                                             O peratio n al g u id elines for n o n-essential   B ased on system secu rity & eq u itab le lo ad
           M an dato ry L o ad sh ed d ing                                          lo ad s                          sh ed d in g in ESK O M co n tro l area

                 G as G eneratio n                                        M u nicipal/ Esko m                                      If availab le

                In terru p tible lo ads                                        C o n tracts                             C ost o f su p p ly op tim izatio n .
                                                                                                                     All m ach in es th at are capable and
        E L1: Eskom generatio n at M C R                                  E sko m G en eratio n                                    availab le.
E sko m g en eration : E n erg y co n strained w ater
                    reso u rces                                           E sko m G en eratio n                      B ased o n W ater resou rces in S A.

   D em an d M arket P articipation C o n tracts                               C o n tracts                            C o n tractual C o st o ptim izatio n .

                                                        O perational R eserves: 1900M W requirem ent
                                                             In tern atio nal & N atio nal (D M P) n on -firm         C on tractu al co sts op tim izatio n &
S u p p lem ental reserves: D em an d + G en eratio n              co n tracts & g en eration sup p ly           g en eratio n p ro d uction cost op tim izatio n
                                                             G en eratio n su p p ly & co ntracted n atio nal         C on tractu al co sts op tim izatio n &
               10-m inu te reserves                                                 DM P                         g en eratio n p ro d uction cost op tim izatio n
               reg u latin g reserv es                                    G eneratio n su p ply                  G en eration p ro d u ction co st o ptim izatio n

                                                               G en eratio n su p p ly & N atio n n o n-firm          C on tractu al co sts op tim izatio n &
                  Instan taneou s                                          co n tracts (D M P)                   g en eratio n p ro d uction cost op tim izatio n

                                                           D em and: Variable M W from day to day
                     Peak lo ad                                          G en eratio n su p p lies                            C o st o f p ro d u ctio n

                     B ase lo ad                                  Im po rts & G en eratio n su p p lies                       C o st o f p ro d u ctio n

             •YTD 4 times the entire emergency merit order has been used
             •YTD 1 mandatory load shedding for an energy shortage (2 hours of 250MW on Jan 6 2006)
             •Frequency has been allowed to decline to 49.6 Hz for a short period of time on a number of
             occasions

                                                                               11
UNSCHEDULED PUMP STORAGE GENERATION

    • Starting of units
      – In order to prevent the IPS spinning reserve from falling below the
        required level
         y Units are available
         y Sufficient water, should be started
      – After a sudden loss of generation or during plant shortages
         y Increase the system frequency above unacceptable low frequency
           levels
             − In order to provide National Control sufficient time to implement other
               corrective actions

      – Unscheduled Pump Storage generation will be limited to the
        minimum time necessary for system security
      – Operation procedures for Pump Storage generation will change as
        the available water supply changes

                                         12
TYPES OF DMP

    • Supplemental reserve
      –Availability
      –Market

    • Emergency DMP
    • Instantaneous DMP
      –49.75 Hz

                      13
SUPPLEMENTAL RESERVE (DMP)

    • Communication
      – NC to instruct
      – NC to inform Regional Control

    • Instructions
      – As per individual contract

    • Implementation
      – Customer implemented as per instruction

    • Cancellation
      – As per instruction period

                                     14
Emergency DMP

    • Short notice from NC
    • Instructed according to ERMO
    • Higher cost than Supplemental DMP
    • Issued as per individual contract

                        15
EMERGENCY LEVEL 1 WARNINGS

    • Maximum Generation Warnings
      – National Control shall issue an Emergency Level 1 Warning
         y Expected shortfall of spinning reserves
      – Sent to:
         y Power Stations
         y Dx Control centres
      – Communicated via SMS
         y Eskom staff

      – Emergency Level 1 Warning will be cancelled as soon as the
        required amount of Spinning Reserve is in hand

                                  16
EMERGENCY LEVEL 1 WARNINGS

    • Generation Responsibility
      – Power Station Control Room shall inform the Senior Shift
        Supervisor who shall organise the internal activity of the
        station such that, during the period of warning:
         y Maximum/Emergency Generation output of the plant is readily
           available
         y The plant is operated in a manner that will allow rapid increase
           to Maximum/Emergency Generation output
         y All testing and maintenance on the control and protection
           systems that may affect the output of the station and can be
           deferred, is halted

                                  17
EL1 GENERATION INSTRUCTIONS

    • Emergency Level 1 in force
       – Instructed:
           y Spinning reserve of 500 MW not met and load is still expected to increase
       – Cancelled:
           y Spinning reserve requirement is met
           y Frequency has returned to 50.0 Hz and is expected to remain there for the next 30
             minutes

    • Units off AGC and go to MCR
    • Limited to specific periods for the various power stations
    • When EL1 is instructed to the power stations it must be
      logged on the facility provided in the control room

                                           18
INTERRUPTIBLE LOAD

    • Interruptible load shedding
       – EL1 in force
       AND
          y Frequency gradually declines below 49.80 Hz and load is still picking up
              or
          y Frequency falls rapidly below 49.5 Hz and does not recover within one
            minute

    • Sufficient interruptible load shall be shed until the
      frequency returns to 50 Hz

                                      19
GAS TURBINE GENERATION

    •       All gas turbines will be armed for under
            frequency starting at all times
    •       Order for deployment of the gas turbines shall
            be as per the ERMO
    •       Unit Starting
        –        Slow frequency decline
             y        Frequency gradually declines below 49.80 Hz and load is still picking up
        –        Fast frequency decline
             y        F < 49.4 Hz for a period longer than 20 seconds
        –        Only the number of gas turbines sufficient to return the frequency to
                 49.7 Hz should be started

    •       Shutdown
        –        When the frequency has returned to 50.0 Hz
        –        Gas turbines shall be taken to SCO mode

                                             20
MUNICIPAL ASSISTANCE

    • Assistance from municipal gas turbines and municipal
      operating oil fired stations will be requested when:
       – Frequency is expected to fall below 49.6 Hz with all other
         emergency measures introduced in the time available

    • Purpose
       – Prevent the frequency from falling below 49.5 Hz

    • Termination
       – When the frequency is restored to 49.7 Hz and is expected to
         remain above 49.7 Hz for the next 30 minutes

                                    21
FREQUENCY RESPONSE

    • Affected by:
      –Spinning reserves
      –Generator governor settings
      –Load characteristic
    • Eskom’s bias
      –125 – 250 MW / 0.1 Hz

                             22
LOAD REDUCTION FOR FREQUENCY CONTROL

    • LOAD REDUCTION SCHEMES
      –Under frequency
         y Automatic

      –Voltage / capacity shortage
         y Manual

                         23
AUTOMATIC SCHEMES

    • Consumer voluntarily automatic under
      frequency load shedding (CVA-U/F-LS)
      – Arrest rapid frequency decline
      – Operated by relays in consumers yards
      – Protect the consumers connected to the MA-/F-LS scheme
      – Three stages
         y 49.2 Hz
         y 49.1 Hz
         y 49.0 Hz
      – 10% of Distribution’s peak

                                24
RESTORATION OF AUTOMATICALLY SHED LOADS

    • CVA UFLS RESTORATION
    • Only shed load that can be restored without
      instruction from National Control
    • Requirements
      – May be restored by the customer without reference to either
        Distributor Network Management or National Control
      – F > 49.5 Hz (Relays will only be reset @ this frequency)

                                25
AUTOMATIC SCHEMES cont.

    • Mandatory automatic under frequency load
      shedding (MA-U/F-LS)
       – Operated by relays in Eskom’s yards
       – Stabilise rapid declines in system frequency that are not corrected
         by the CVA-U/F-LS scheme.
       – A total of 40 % of the IPS load must be connected to U/F relays set
         at four frequency stages (10 % each stage)
          y 48.8 Hz
          y 48.5 Hz
          y 48.2 Hz
          y 47.9 Hz
       – The MA-U/F-LS scheme must be applied to every Distribution
         network
       – CVA-U/F-LS consumers should be omitted from this scheme or
         connected at the lower frequency levels

                                    26
MANUAL REDUCTIONS

    •       Purpose
        –       Stabilise gradual declines in system frequency
            y        By reducing load on a pro rata basis in all Distribution networks
                −          Through curtailment or shedding

    •       Two categories
        –       Load curtailment
            y        Disconnected voluntarily by consumers
            y        Within a set time delay (1 hour)
            y        Following an instruction by National Control to reduce load
        –       Load shedding
            y        Shed manually at convenient points on the distribution system
            y        Within a set time delay (10 min)
            y        Following an instruction by National Control to shed load or reduce load
        –       Time delay for load shedding is appreciably less than the time delay
                for load curtailment

                                             27
Load Reduction

                                              MANUAL LOAD REDUCTION

                             MANUAL
                                                                                LOAD CURTAILMENT
                          LOAD SHEDDING

                                          Not selective                          Action taken      Selective for
     Short Notice      Action by Eskom                     Longer notice
                                          for consumer                           by customer        consumer

                                                                      Minimum 1 hour
              Within 10 min
                                                                        notification

                                                   28
LOAD REDUCTION INSTRUCTION

    • Instructed as far in advance as possible
      – Time that the reduction is to commence
      – Amount of load
      – Expected duration
    • If the load profile changes NCC will cancel the
      instruction before the time
    • Restoration only takes place on instruction from
      NC

                               29
LOAD REDUCTION ACTIONS

    • Distribution
      – Distribution networks may decide whether to approach consumers for load
        curtailment or to shed load manually on a pro rata basis to achieve the
        requested load reduction at the required time
      – Consumers on curtailment must be notified and instructed to curtail desired
        amount of load at specified time
          y This must be verified
      – Load reduction must take place at specified time
      – Recording and reporting must take place

    • Municipalities
      – Own generation should be included in the group of consumers who form
        part of the load curtailment scheme
      – Should be requested to reduce their import when the load curtailment
        instruction is given
      – Required municipal reduction (in %) should not be less than the
        municipalities’ percentage of the total Regional demand

                                      30
LOAD SHEDDING WARNING

    • It will not always be possible to give
      a load shedding warning
    • As far in advance as possible
      –Time of warning
      –Amount of load expected
      –NOT expected start time
      –NOT expected duration

                          31
WARNING ACTIONS

    • Distribution actions
      –Prepare for load shedding
      –One hour after the warning
         y Distribution NMCs shall be able to reduce the required
           amount of load within 10 minutes by load shedding.
      –This warning enables the Distribution NMCs to
       prepare their plans for load shedding
      –Preferably no action (i.e. contacting customers)
       must be taken when the warning is received

                               32
LOAD SHEDDING INSTRUCTION

    • Indications
      – Immediate load reduction is required

    • Instruction
      – Shed amount of required load

    • Sufficient load shall be shed to return the
      frequency to 49.7 Hz

                                33
LOAD SHEDDING ACTIONS

    • Distribution
      –The requested load must be shed within 10 min
         y If exact amount cannot be shed select the higher of the
           two options

      –Recording and reporting must take place

                               34
RECORDING AND REPORTING

    • Recording/logging
      – Which loads were reduced
      – Time breaker opened
      – Time breaker closed

    • Report back
      – Amount of load reduced
      – Time requested load reduced

                                 35
RESTORATION OF MANUALLY SHED LOADS

     •       RESTORATION
         –       Gradually restored on instruction from National
                 Control via the Distributor Network Management
                 Centres
             y      If the exact amount cannot be restored select the
                    lower of the two options
         –       Frequency is seen to be recovering to 50.0 Hz
             AND
         –       F > 49.7 Hz

                                     36
ORDER OF RESTORATION OF ALL LOADS SHED

    • Requirements
       – Restoration of the majority of load shed by the mandatory automatic UFLS
         scheme will have priority over loads shed by the manual UFLS scheme

    • Restoration sequence
       – Mandatory UFLS stage 4
       – Mandatory UFLS stage 3
       – Mandatory UFLS stage 2
       – Mandatory UFLS stage 1
       – CVA UFLS
       – Manual LS
       – Load curtailment
       – Manual load shedding/curtailment may take place to replace load, which was
         shed by the different stages of the Mandatory UFLS Scheme

                                      37
END
THANK YOU
You can also read