IntesisBox BACnet IP Server - User Manual
←
→
Page content transcription
If your browser does not render page correctly, please read the page content below
IntesisBox® BACnet IP Server
Panasonic Air Conditioning
User Manual
Issu Date: 03/0215
r2.1 engIntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
© Intesis Software S.L. 2015 All Rights Reserved.
Information in this document is subject to change without notice. The software described in this document is
furnished under a license agreement or nondisclosure agreement. The software may be used only in accordance
with the terms of those agreements. No part of this publication may be reproduced, stored in a retrieval system or
transmitted in any form or any means electronic or mechanical, including photocopying and recording for any
purpose other than the purchaser’s personal use without the written permission of Intesis Software S.L.
Intesis Software S.L.
Milà i Fontanals, 1 bis
08700 Igualada
Spain
TRADEMARKS
All trademarks and trade names used in this document are acknowledged to be the copyright of their respective
holders.
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 2/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
Gateway for the integration of Panasonic air conditioning
systems in BACnet/IP enabled monitoring and control systems.
Different models are available for this gateway, with the following Order Codes:
PA-AC-BAC-64
Model supporting up to 64 indoor units.
PA-AC-BAC-128
Model supporting up to 128 indoor units.
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 3/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
INDEX
1 Description ............................................................................................................................................................ 7
1.1 Introduction .................................................................................................................................................... 7
1.2 Functionality .................................................................................................................................................. 8
1.3 Capacity of IntesisBox ................................................................................................................................... 8
2 Protocol Implementation Conformance Statement ............................................................................................... 9
2.1 BACnet Standardized Device Profile (Annex L): ........................................................................................... 9
2.2 Segmentation Capability: .............................................................................................................................. 9
2.3 Data Link Layer Options: ............................................................................................................................... 9
2.4 Device Address Binding: ............................................................................................................................. 10
2.5 Networking Options: .................................................................................................................................... 10
2.6 Character Sets Supported ........................................................................................................................... 10
2.7 Gateway ...................................................................................................................................................... 10
3 BACnet Interoperability Building Blocks Supported (BIBBs) .............................................................................. 11
3.1 Data Sharing BIBBs .................................................................................................................................... 11
3.2 Alarm and Event Management BIBBs ......................................................................................................... 11
3.3 Scheduling BIBBs ........................................................................................................................................ 12
3.4 Trending BIBBs ........................................................................................................................................... 12
3.5 Network Management BIBBs ...................................................................................................................... 12
3.6 Device Management BIBBs ........................................................................................................................ 13
4 Service Types ..................................................................................................................................................... 14
5 Objects ................................................................................................................................................................ 15
5.1 Supported Object Types .............................................................................................................................. 15
5.2 Member objects ........................................................................................................................................... 16
5.2.1 Type: Gateway ..................................................................................................................................... 16
5.2.2 Type: Central control ........................................................................................................................... 16
5.2.3 Type: Indoor Unit ................................................................................................................................. 16
5.3 Objects and properties ................................................................................................................................ 17
5.3.1 Panasonic AC Gateway (Device Object Type) .................................................................................... 18
5.3.2 AdaptorLink1_ErrorCode (Multistate Input Object Type) .................................................................... 20
5.3.3 AdaptorLink2_ErrorCode (Multistate Input Object Type) .................................................................... 21
5.3.4 OnOff_All (Binary Output Object Type) ............................................................................................... 24
5.3.5 Mode_All (Multistate Output Object Type) ........................................................................................... 25
5.3.6 SetPoint_All (Analog Output Object Type) .......................................................................................... 26
5.3.7 FanSpeed_All (Multistate Output Object Type) ................................................................................... 27
5.3.8 RemoteControl_Lock_All (Multistate Output Object Type) .................................................................. 28
5.3.9 Consumption_Reset (Binary Output Object Type) .............................................................................. 30
5.3.10 Occupancy_All (Multistate Output Object Type) ................................................................................. 31
5.3.11 Occ_Cool_Setpoint (Analog Value Object Type) ................................................................................ 32
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 4/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
5.3.12 Occ_Heat_Setpoint (Analog Value Object Type) ................................................................................ 33
5.3.13 Unocc_Cool_Setpoint (Analog Value Object Type) ............................................................................ 34
5.3.14 Unocc_Heat_Setpoint (Analog Value Object Type) ............................................................................ 35
5.3.15 Occ_ContinuousCheck (Binary Output Object Type) .......................................................................... 36
5.3.16 Unocc_DeadbandAction (Binary Output Object Type) ........................................................................ 37
5.3.17 IUxxx_IU_Exist (Binary Input Object Type) ......................................................................................... 38
5.3.18 IUxxx_OnOff_status (Binary Input Object Type) ................................................................................. 39
5.3.19 IUxxx_OnOff_command (Binary Output Object Type) ........................................................................ 40
5.3.20 IUxxx_Mode_status (Multistate Input Object Type) ............................................................................. 41
5.3.21 IUxxx_Mode_command (Multistate Output Object Type) .................................................................... 42
5.3.22 IUxxx_Setpoint_status (Analog Input Object Type) ............................................................................. 43
5.3.23 IUxxx_Setpoint_command (Analog Output Object Type).................................................................... 44
5.3.24 IUxxx_Room_Temperature (Analog Input Object Type) ..................................................................... 45
5.3.25 IUxxx_FanSpeed_status (Multistate Input Object Type) ..................................................................... 46
5.3.26 IUxxx_FanSpeed_command (Multistate Output Object Type) ............................................................ 47
5.3.27 IUxxx_AirDirection_status (Multistate Input Object Type) ................................................................... 48
5.3.28 IUxxx_IU_AirDirection_command (Multistate Output Object Type) .................................................... 49
5.3.29 IUxxx_FilterSign_status (Binary Input Object Type) ............................................................................ 50
5.3.30 IUxxx_FilterSing_Reset_command (Binary Output Object Type) ....................................................... 51
5.3.31 Uxxx_ErrorCode (Multistate Input Object Type) .................................................................................. 52
5.3.32 IUxxx_RemoteControl_Lock (Multistate Value Object Type) .............................................................. 55
5.3.33 IUxxx_Occupancy (Multistate Value Object Type) .............................................................................. 57
5.3.34 IUxxx_Consumption_Yesterday (Analog Input Object Type) .............................................................. 58
5.3.35 IUxxx_Consumption_Today (Analog Input Object Type) .................................................................... 59
5.3.36 IUxxx_Consumption_Total (Analog Input Object Type) ...................................................................... 60
6 Connections ........................................................................................................................................................ 61
6.1 Power device ............................................................................................................................................... 62
6.2 Connect to BACnet ...................................................................................................................................... 62
6.3 Connect to CZ-CFUNC2 communication adaptor interface ........................................................................ 62
6.4 Connect to PC (LinkBoxBACnet) ................................................................................................................ 63
6.5 Connect a Wattmeter to the CZ-CFUNC2 ................................................................................................... 63
7 Set-up process and troubleshooting ................................................................................................................... 64
7.1 Pre-requisites .............................................................................................................................................. 64
7.2 LinkBoxBACnet. Configuration & monitoring tool for IntesisBox BACnet series ........................................ 64
7.2.1 Introduction .......................................................................................................................................... 64
7.2.2 Connections configuration ................................................................................................................... 64
7.2.2.1 Connnection tab ........................................................................................................................... 65
7.2.2.2 Discover function .......................................................................................................................... 67
7.2.2.3 Signals .......................................................................................................................................... 68
7.2.2.4 Occupancy ................................................................................................................................... 69
7.2.2.5 Consumption ................................................................................................................................ 70
7.2.3 Sending the configuration to IntesisBox .............................................................................................. 72
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 5/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
7.2.4 Signals viewer ...................................................................................................................................... 72
7.2.5 Files ..................................................................................................................................................... 73
7.2.6 Set-up procedure ................................................................................................................................. 74
7.3 Physical checking ........................................................................................................................................ 75
7.4 Software checking ....................................................................................................................................... 75
7.5 256, 257 and 258 Error ............................................................................................................................... 76
8 AC Unit Types compatibility ................................................................................................................................ 77
9 Mechanical & electrical characteristics ............................................................................................................... 77
10 Dimensions ......................................................................................................................................................... 78
11 Error codes .......................................................................................................................................................... 79
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 6/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
1 Description
1.1 Introduction
This document describes the integration of Panasonic air conditioning systems into BACnet compatible devices
and systems using gateway IntesisBox BACnet/IP Server – Panasonic.
The aim of this integration is to monitor and control your Panasonic air conditioning system, remotely, from your
Control Center using any commercial SCADA or monitoring software that includes a BACnet/IP driver. To do it so,
IntesisBox allows BACnet/IP communication, acting as a server, allowing polling or subscription requests (COV).
IntesisBox makes available the Panasonic air conditioning system indoor units through independent BACnet
objects.
Abstraction of Panasonic air conditioning system properties and functionalities as fixed BACnet Objects. IntesisBox
allows fixed BACnet object IDs mapping. Simple configuration is needed: just select the appropriate communication
parameters (IP address, baud rate…).
1
IntesisBox connects to the Panasonic CZ-CFUNC2 communication adaptor .
Up to 128 indoor units supported.
This document assumes that the user is familiar with BACnet and Panasonic technologies and their technical
terms.
Up to 30 Up to 64
Outdoor units Indoor units
BACnet IP
client BACnet/IP
Ethernet EIA485 Link1 U1U2
LAN PA-AC-BAC-64/128
TCP/IP Link 2 U1U2
BACnet IP CZ-CFUNC2
client
EIA232
or Up to 30 Up to 64
Ethernet Outdoor units Indoor units
LinkBoxBacnet
Configuration Only needed for configuration
Software
1
CZ-CFUNC2 is an accessory provided by Panasonic and should be acquired separately.
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 7/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
1.2 Functionality
®
IntesisBox continuously polls (reads) the Panasonic CZ-CFUNC2 communication adaptor for all configured
signals and keeps the updated status of all of them in its memory, ready to be served when requested from the
BACnet side.
The role of IntesisBox consists in associate the elements of the CZ-CFUNC2 communication adaptor with BACnet
objects.
The control of the indoor units through the CZ-CFUNC2 communication adaptor is permitted, so commands toward
the CZ-CFUNC2 communication adaptor are permitted.
Each indoor unit is offered in set of BACnet objects.
Element Object supported
Status
Command
Indoor Unit
Error
Exist
Adaptor Error
1.3 Capacity of IntesisBox
IntesisBox is capable of integrating one single CZ-CFUNC2 communication adaptor and its associated elements.
Element Max. Notes
IntesisBox can only integrate one single CZ-CFUNC2
Number of adaptors 1
communication adaptor.
Number of indoor units that can be controlled through
Number of indoor units 128 *
IntesisBox
Number of Objects 2575 * Number of CZ-CFUNC2 objects available into IntesisBox.
®
* There are two different models of IntesisBox BAC – Panasonic AC each one with different capacity. The table
above shows the capacity for the top model (with maximum capacity).
Their order codes are:
PA-AC-BAC-64: Model supporting up to 64 indoor units
PA-AC-BAC-128: Model supporting up to 128 indoor units
Regarding the CZ-CFUNC2 communication adaptor, below there is a summary table indicating different capacities
for each element.
Element Value ranges Description
Indoor Units 1 to 128 Number of indoor units supported by IntesisBox
Adaptor 1 Number of adaptors supported by IntesisBox
Links 1 to 2 Number of links supported by IntesisBox
Outdoor Units 1 to 60 Number of outdoor units supported by IntesisBox
The number of adaptors is fixed. The number of Indoor Units, Links and Outdoor Units may vary on each project.
These parameters can be configured through LinkBoxBACnet (See section 7.2).
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 8/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
2 Protocol Implementation Conformance Statement
BACnet Protocol Implementation Conformance Statement (PICS)
Date: 2013-03-22
Vendor Name: Intesis Software SL
Product Name: IntesisBox-BACnet-Panasonic AC
Product Model Number: PA-AC-BAC-64/128
Application Software Version: 4.0.1
Firmware Revision: 4.0.1
BACnet Protocol Revision: 2
Product Description:
Panasonic air conditioning system -BACnet/IP Gateway
Abstraction of Panasonic air conditioning system through CZ-CFUNC2 communication adaptor properties and
functionalities as BACnet Objects.
Capacity of 1 CZ-CFUNC2 communication adaptor and all signals from associated indoor units.
2.1 BACnet Standardized Device Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
Additional BACnet Interoperability Building Blocks Supported (Annex K):
Reference of BIBBs List
2.2 Segmentation Capability:
Segmented request supported No Yes Window Size · ·
Segmented responses supported No Yes Window Size · ·
2.3 Data Link Layer Options:
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) ____
MS/TP master (Clause 9), baud rate(s):
MS/TP slave (Clause 9), baud rate(s):
Point-To-Point, EIA 232 (Clause 10), baud rate(s):
Point-To-Point, modem, (Clause 10), baud rate(s):
LonTalk, (Clause 11), medium: _____
Other:
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 9/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
2.4 Device Address Binding:
Is static device binding supported? (This is currently necessary for two-way communication with
MS/TP slaves and certain other devices.) Yes No
2.5 Networking Options:
Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
Annex H, BACnet Tunneling Router over IP
BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices? Yes No
2.6 Character Sets Supported
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
ANSI X3.4
IBM™/Microsoft™ DBCS
JIS C 6226
ISO 10646 (UCS-4)
ISO 10646 (UCS-2)
ISO 8859-1
2.7 Gateway
If this product is a communication gateway, describe the types of non-BACnet equipment/network(s) that the gateway
supports:
Panasonic CZ-CFUNC2 communication adaptor through EIA485 interface
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 10/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
3 BACnet Interoperability Building Blocks Supported (BIBBs)
3.1 Data Sharing BIBBs
BIBB Type Active BACnet Service Initiate Execute
DS-RP-A Data Sharing-ReadProperty–A ReadProperty
DS-RP-B Data Sharing-ReadProperty–B ReadProperty
DS-RPM-A Data Sharing-ReadPropertyMultiple–A ReadPropertyMultiple
DS-RPM-B Data Sharing-ReadPropertyMultiple–B ReadPropertyMultiple
DS-RPC-A Data Sharing-ReadPropertyConditiona–A ReadPropertyConditional
DS-RPC-B Data Sharing-ReadPropertyConditional–B ReadPropertyConditional
DS-WP-A Data Sharing-WriteProperty–A WriteProperty
DS-WP-B Data Sharing-WriteProperty–B WriteProperty
DS-WPM-A Data Sharing-WritePropertyMultiple–A WritePropertyMultiple
DS-WPM-B Data Sharing-WritePropertyMultiple–B WritePropertyMultiple
SubscribeCOV
DS-COV-A Data Sharing-COV–A ConfirmedCOVNotification
UnconfirmedCOVNotification
SubscribeCOV
DS-COV-B Data Sharing-COV–B ConfirmedCOVNotification
UnconfirmedCOVNotification
SubscribeCOVProperty
DS-COVP-A Data Sharing-COVP–A ConfirmedCOVNotification
UnconfirmedCOVNotification
SubscribeCOVProperty
DS-COVP-B Data Sharing-COVP–B ConfirmedCOVNotification
UnconfirmedCOVNotification
DS-COVU-A Data Sharing-COV-Unsolicited–A UncofirmedCOVNotification
DS-COVU-B Data Sharing-COV-Unsolicited-B UncofirmedCOVNotification
3.2 Alarm and Event Management BIBBs
BIBB Type Active BACnet Service Initiate Execute
ConfirmedEventNotification
AE-N-A Alarm and Event-Notification–A
UnconfirmedEventNotification
ConfirmedEventNotification
AE-N-I-B Alarm and Event-Notification Internal–B
UnconfirmedEventNotification
ConfirmedEventNotification
AE-N-E-B Alarm and Event-Notification External–B
UnconfirmedEventNotification
AE-ACK-A Alarm and Event-ACK–A AcknowledgeAlarm
AE-ACK-B Alarm and Event-ACK–B AcknowledgeAlarm
AE-ASUM-A Alarm and Event-Summary–A GetAlarmSummary
AE-ASUM-B Alarm and Event-Summary–B GetAlarmSummary
AE-ESUM-A Event-Summary–A GetEnrollmentSummary
AE-ESUM-B Event-Summary–B GetEnrollmentSummary
AE-INFO-A Alarm and Event-Information–A GetEventInformation
AE-INFO-B Alarm and Event-Information–B GetEventInformation
AE-LS-A Alarm and Event-LifeSafety–A LifeSafetyOperation
AE-LS-B Alarm and Event-LifeSafety–B LifeSafetyOperation
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 11/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
3.3 Scheduling BIBBs
BIBB Type Active BACnet Service Initiate Execute
Scheduling–A
SCHED-A
(must support DS-RP-A and DS-WP-A)
Scheduling-Internal–B
SCHED-I-B (shall support DS-RP-B and DS-WP-B)
(shall also support ether DM-TS-B or DS-UTC-B)
Scheduling-External–B
SCHED-E-B
(shall support SCHED-I-B and DS-WP-A)
T-VMT-A Trending - Viewing and Modifying Trends–A ReadRange
T-VMT-I-B Trending - Viewing and Modifying Trends Inernal–B ReadRange
T-VMT-E-B Trending - Viewing and Modifying Trends External–B ReadRange
ConfirmedEventNotification
T-ATR-A Trending - Automated Trend Retrieval–A
ReadRange
ConfirmedEventNotification
T-ATR-B Trending - Automated Trend Retrieval–B
ReadRange
3.4 Trending BIBBs
BIBB Type Active BACnet Service Initiate Execute
T-VMT-A Trending - Viewing and Modifying Trends–A ReadRange
T-VMT-I-B Trending - Viewing and Modifying Trends Inernal–B ReadRange
T-VMT-E-B Trending - Viewing and Modifying Trends External–B ReadRange
ConfirmedEventNotification
T-ATR-A Trending - Automated Trend Retrieval–A
ReadRange
ConfirmedEventNotification
T-ATR-B Trending - Automated Trend Retrieval–B
ReadRange
3.5 Network Management BIBBs
BIBB Type Active BACnet Service Initiate Execute
Establish-Connection-To-
Network Management - Connection Network
NM-CE-A
Establishment–A Disconnect-Connection-To-
Network
Establish-Connection-To-
Network Management - Connection Network
NM-CE-B
Establishment– B Disconnect-Connection-To-
Network
Who-Is-Router-To-Network
I-Am-Router-To-Network
I-Could-Be-Router-To-
NM-RC-A Network Management - Router Configuration–A
Network
Initialize-Routing-Table
Initialize-Routing-Table-Ack
Who-Is-Router-To-Network
I-Am-Router-To-Network
NM-RC-B Network Management - Router Configuration–B
Initialize-Routing-Table
Initialize-Routing-Table-Ack
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 12/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
3.6 Device Management BIBBs
BIBB Type Active BACnet Service Initiate Execute
Who-Is
DM-DDB-A Device Management - Dynamic Device Binding–A
I-Am
Who-Is
DM-DDB-B Device Management - Dynamic Device Binding–B
I-Am
Who-Has
DM-DOB-A Device Management - Dynamic Object Binding–A
I-Have
Who-Has
DM-DOB-B Device Management - Dynamic Object Binding–B
I-Have
DM-DCC-A Device Management - DeviceCommunicationControl–A DeviceCommunicationControl
DM-DCC-B Device Management - DeviceCommunicationControl–B DeviceCommunicationControl
ConfirmedPrivateTransfer
DM-PT-A Device Management - PrivateTransfer–A
UnconfirmedPrivateTransfer
ConfirmedPrivateTransfer
DM-PT-B Device Management - PrivateTransfer–B
UnconfirmedPrivateTransfer
ConfirmedTextMessage
DM-TM-A Device Management - Text Message–A
UnconfirmedTextMessage
ConfirmedTextMessage
DM-TM-B Device Management - Text Message–B
UnconfirmedTextMessage
DM-TS-A Device Management - TimeSynchronization–A TimeSynchronization
DM-TS-B Device Management - TimeSynchronization–B TimeSynchronization
DM-UTC-A Device Management - UTCTimeSynchronization–A UTCTimeSynchronization
DM-UTC-B Device Management - UTCTimeSynchronization–B UTCTimeSynchronization
DM-RD-A Device Management - ReinitializeDevice–A ReinitializeDevice
DM-RD-B Device Management - ReinitializeDevice–B ReinitializeDevice
AtomicReadFile
AtomicWriteFile
DM-BR-A Device Management - Backup and Restore–A
CreateObject
ReinitializeDevice
AtomicReadFile
DM-BR-B Device Management - Backup and Restore–B AtomicWriteFile
ReinitializeDevice
DM-R-A Device Management - Restart–A UnconfimedCOVNotification
DM-R-B Device Management - Restart–B UnconfimedCOVNotification
AddListElement
DM-LM-A Device Management - List Manipulation–A
RemoveListElement
AddListElement
DM-LM-B Device Management - List Manipulation–B
RemoveListElement
CreateObject
DM-OCD-A Device Management - Object Creation and Deletion–A
DeleteObject
CreateObject
DM-OCD-B Device Management - Object Creation and Deletion–B
DeleteObject
VT-Open
DM-VT-A Device Management - Virtual Terminal–A VT-Close
VT-Data
VT-Open
DM-VT-B Device Management - Virtual Terminal–B VT-Close
VT-Data
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 13/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
4 Service Types
Service type Service name Supported Remarks
AcknowledgeAlarm
ConfirmedCOVNotification
Alarm and Event ConfirmedEventNotification
Services GetAlarmSummary
GetEnrollmentSummary
SubscribeCOV
AtomicReadFile
File Access Services
AtomicWriteFile
AddListElement
RemoveListElement
CreateObject
DeleteObject
Object Access ReadProperty
Services ReadPropertyConditional
ReadPropertyMultiple
ReadRange
WriteProperty
WritePropertyMultiple
DeviceComminicationControl
Remote Device
ConfirmedPrivateTransfer
Management
Services ConfirmedTextMessage
ReinitializeDevice
VtOpen
Virtual Terminal
Services VtClose
VtData
Authenticate
Security Services
RequestKey
I-Am
I-Have
UnconfirmedCOVNotification
UnconfirmedEventNotification
UnconfirmedPrivateTransfer
UnconfirmedTextMessage
Unconfirmed
Services TimeSynchronization
UtcTimeSynchronization
Who-Has
Who-Is
LifeSafetyOperation
SubscribeCOVProperty
GetEventInformation
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 14/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
5 Objects
5.1 Supported Object Types
The objects supported are shown in the table below.
Object Type ID Supported Management Point
IUxxx_SetPoint_status
IUxxx_Room_Temperature
Analog-Input 0 IUxxx_Consumption_Yesterday
IUxxx_Consumption_Today
IUxxx_Consumption_Total
SetPoint_All
Analog-Output 1
IUxxx_SetPoint_command
Occ_Cool_SetPoint
Occ_Heat_SetPoint
Analog-Value 2
Unocc_Cool_SetPoint
Unocc_Heat_SetPoint
Averaging 18
IUxxx_IU_Exist
Binary-Input 3 IUxxx_OnOff_status
IUxxx_FilterSign_status
OnOff_All
Occ_ContinuousCheck
Unocc_DeadbandAction
Binary-Output 4
Consumption_Reset
IUxxx_OnOff_command
IUxxx_FilterSign_Reset_command
Binary-Value 5
Calendar 6
Command 7
Device 8 Panasonic AC Gateway
Event-Enrollment 9
File 10
Group 11
Life-Safety-Point 21
Life-Safety-Zone 22
Loop 12
AdaptorLink1_ErrorCode
AdaptorLink2_ErrorCode
IUxxx_Mode_status
Multistate-Input 13
IUxxx_FanSpeed_status
IUxxx_AirDirection_status
IUxxx_ErrorCode
Mode_All
FanSpeed_All
RemoteControl_Lock_All
Multistate-Output 14 Occupancy_All
IUxxx_Mode_command
IUxxx_FanSpeed_command
IUxxx_AirDirection_command
IUxxx_RemoteControl_Lock
Multistate-Value 19
IUxxx_Occupancy
Notification-Class 15
Program 16
Schedule 17
Trend-Log 20
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 15/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
5.2 Member objects
5.2.1 Type: Gateway
Object-name Description Object-type Object-instance
Panasonic AC Gateway Panasonic AC Gateway Device 246
AdaptorLink1_ErrorCode AdaptorLink1_ErrorCode MI 16
AdaptorLink2_ErrorCode AdaptorLink2_ErrorCode MI 17
5.2.2 Type: Central control
Object-name Description Object-type Object-instance
OnOff_All OnOff_All BO 18
Mode_All Mode_All MO 19
SetPoint_All SetPoint_All AO 20
FanSpeed_All FanSpeed_All MO 21
RemoteControl_Lock_All RemoteControl_Lock_All MO 22
Occupancy_All Occupancy_All MO 23
Occ_Cool_SetPoint Occ_Cool_SetPoint AV 24
Occ_Heat_SetPoint Occ_Heat_SetPoint AV 25
Unocc_Cool_SetPoint Unocc_Cool_SetPoint AV 26
Unocc_Heat_SetPoint Unocc_Heat_SetPoint AV 27
Occ_ContinuousCheck Occ_ContinuousCheck BO 28
Unocc_DeadbandAction Unocc_DeadbandAction BO 29
Consumption_Reset Consumption_Reset BO 34
5.2.3 Type: Indoor Unit
Object-name Description Object-type Object-instance
IUxxx_IU_Exist K-OA-IA_IU_Exist BI (xxx * 256) + 0
IUxxx_OnOff_status K-OA-IA_OnOff_status BI (xxx * 256) + 1
IUxxx_OnOff_command K-OA-IA_OnOff_command BO (xxx * 256) + 2
IUxxx_Mode_status K-OA-IA_Mode_status MI (xxx * 256) + 3
IUxxx_Mode_command K-OA-IA_Mode_command MO (xxx * 256) + 4
IUxxx_SetPoint_status K-OA-IA_SetPoint_status AI (xxx * 256) + 5
IUxxx_SetPoint_command K-OA-IA_SetPoint_command AO (xxx * 256) + 6
IUxxx_Room_Temperature K-OA-IA_Room_Temperature AI (xxx * 256) + 7
IUxxx_FanSpeed_status K-OA-IA_FanSpeed_status MI (xxx * 256) + 8
IUxxx_FanSpeed_command K-OA-IA_FanSpeed_command MO (xxx * 256) + 9
IUxxx_AirDirection_status K-OA-IA_AirDirection_status MI (xxx * 256) + 10
IUxxx_AirDirection_command K-OA-IA_AirDirection_command MO (xxx * 256) + 11
IUxxx_FilterSign_status K-OA-IA_FilterSign_status BI (xxx * 256) + 12
IUxxx_FilterSign_Reset_command K-OA-IA_FilterSign_Reset_command BO (xxx * 256) + 13
IUxxx_ErrorCode K-OA-IA_ErrorCode MI (xxx * 256) + 14
IUxxx_RemoteControl_Lock K-OA-IA_RemoteControl_Lock MV (xxx * 256) + 15
IUxxx_Occupancy K-OA-IA_Occupancy MV (xxx * 256) + 30
IUxxx_Consumption_Yesterday K-OA-IA_Consumption_Yesterday AI (xxx * 256) + 31
IUxxx_Consumption_Today K-OA-IA_Consumption_Today AI (xxx * 256) + 32
IUxxx_Consumption_Total K-OA-IA_Consumption_Total AI (xxx * 256) + 33
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 16/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
5.3 Objects and properties
Below you can find relevant information for the objects and properties.
Object_Identifier: In the Device Object, the value of object instance is configurable through LinkBoxBACnet.
See Table 5.1 in order to obtain the name of each object.
Variable Description
"xxx" Indoor Unit identifier (1..128)
"k" Link number (1..2)
"OA" Outdoor Unit address (1..30)
"IA" Indoor Unit address (1..64)
Table 5.1 Objects and properties variables and descriptions
Object_Name: In the Device Object, this string is configurable through LinkBoxBACnet. See Table 5.1 in order
to obtain the name of each object.
Description: In the Device Object, this string is configurable through LinkBoxBACnet. See Table 5.1 in order to
obtain the description of each object.
Relinquish_Default: In Binary Outputs, Multistate Outputs and Multistate Values, the value of
Present_Value property will be read.
Priority_Array: In Binary Outputs, Multistate Outputs and Multistate Values, Priority_Array[16] will acquire
the value of Present_Value property and Priority_Array[1]~[15] will be NULL.
State_Text: In Multistate Outputs, Multistate Outputs and Multistate Values, it cannot be read the whole
array at once, so “Array Index” must be specified in order to obtain the text of the corresponding state.
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 17/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
5.3.1 Panasonic AC Gateway (Device Object Type)
Property Identifier Property Datatype Value ASHRAE IBOX
Object_Identifier BACnetObjectIdentifier (Device, 246) R R
Object_Name CharacterString "Panasonic AC Gateway" R R
Object_Type BACnetObjectType DEVICE (8) (Device Object Type) R R
System_Status BACnetDeviceStatus OPERATIONAL (0) R R
Vendor_Name CharacterString "Intesis Software" R R
Vendor_Identifier Unsigned16 246 R R
Model_Name CharacterString "IntesisBox_BACNET_SVR_Panasonic" R R
Firmware_Revision CharacterString "4.0.4" R R
Application_Software_
CharacterString "4.0.4" R R
Version
Location CharacterString "" O R
Description CharacterString "Panasonic AC Gateway" O R
Protocol_Version Unsigned 1 R R
Protocol_Revision Unsigned 2 R R
Protocol_Services_
BACnetServiceSupported Refer to section 4 [Service Types]. R R
Supported
Protocol_Object_Types_ BACnetObjectTypes
Refer to section 5.1 [Object Types]. R R
Supported Supported
BACnetArray[N] of
Object_List BACnetARRAY[N] R R
BACnetObjectIdentifier
BACnetArray[N] of
Structured_Object_List - O -
BACnetObjectIdentifier
Max_APDU_Length_
Unsigned 480 R R
Accepted
Segmentation_Supported BACnetSegmentation NO_SEGMENTATION (3) R R
Max_Segments_
Unsigned - O -
Accepted
VT_Classes_Supported List of BACnetVTClass - O -
Active_VT_Sessions List of BACnetVTSession - O -
Local_Date Date - O -
Local_Time Time - O -
UTC_Offset INTEGER - O -
Daylight_Savings_Status BOOLEAN - O -
APDU_Segment_Timeout Unsigned - O -
APDU_Timeout Unsigned 3,000 R R
Number_of_APDU_
Unsigned 3 R R
Retries
List_Of_Session_Keys List of BACnetSessionKey - O -
Time_Synchronization_
List of BACnetRecipient - O -
Recipients
Max_Master Unsigned - O -
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 18/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
Max_Info_Frames Unsigned - O -
Device_Address_Binding List of BACnetAddressBinding NULL (empty) R R
Database_Revision Unsigned 0 R R
BACnetArray[N] of
Configuration_Files - O -
BACnetObjectIdentifier
Last_Restore_Time BACnetTimeStamp - O -
Backup_Failure_Timeout Unsigned16 - O -
Active_COV_ List of
- O -
Subscriptions BACnetCOVSubscription
Slave_Proxy_Enable BACnetArray[N] of BOOLEAN - O -
Manual_Slave_Address_
List of BACnetAddressBinding - O -
Binding
Auto_Slave_Discovery BACnetArray[N] of BOOLEAN - O -
Slave_Address_Binding BACnetAddressBinding - O -
Last_Restart_Reason BACnetRestartReason - O -
Time_Of_Device_Restart BACnetTimeStamp - O -
Restart_Notification_
List of BACnetRecipient - O -
Recipients
UTC_Time_
Synchronization_ List of BACnetRecipient - O -
Recipients
Time_Synchronization_
Unsigned - O -
Interval
Align_Intervals BOOLEAN - O -
Interval_Offset Unsigned - O -
Max_Segments_accepted Unsigned - O -
Profile_Name CharacterString - O -
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 19/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
5.3.2 AdaptorLink1_ErrorCode (Multistate Input Object Type)
It indicates the communication status of the Link1 on the CZ-CFUNC2 communication adaptor. See section 11 for
more details.
Property Identifier Property Datatype Value ASHRAE IBOX
Object_Identifier BACnetObjectIdentifier (Multi-state Input, 16) R R
Object_Name CharacterString “AdaptorLink1_ErrorCode” R R
Object_Type BACnetObjectType MULTISTATE_INPUT (13) R R
Present_Value Unsigned 1 ~ 259 R R
Description CharacterString “AdaptorLink1_ErrorCode” O R
Device_Type CharacterString "Panasonic AC Gateway" O R
Status_Flags BACnetStatusFlags {FALSE, FALSE, FALSE, TRUE/FALSE} R R
Event_State BACnetEventState STATE_NORMAL (0) R R
Reliability BACnetReliability NO_FAULT_DETECTED (0) O R
Out_Of_Service BOOLEAN FALSE/TRUE R R
Number_Of_States Unsigned 259 R R
BACnetArray[32] of
State_Text Check Communication Status table below. O R
CharacterString
Time_Delay Unsigned - O -
Notification_Class Unsigned - O -
Alarm_Values List of Unsigned - O -
Fault_Values List of Unsigned - O -
Event_Enable BACnetEventTransitionBits - O -
Acked_Transitions BACnetEventTransitionBits - O -
Notify_Type BACnetNotifyType - O -
BACnetArray[N] of
Event_Time_Stamps - O -
BACnetTimeStamp
Profile_Name CharacterString - O -
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 20/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
5.3.3 AdaptorLink2_ErrorCode (Multistate Input Object Type)
It indicates the communication status of the Link2 on the CZ-CFUNC2 communication adaptor. See section 11 for
more details.
Property Identifier Property Datatype Value ASHRAE IBOX
Object_Identifier BACnetObjectIdentifier (Multi-state Input, 17) R R
Object_Name CharacterString “AdaptorLink2_ErrorCode” R R
Object_Type BACnetObjectType MULTISTATE_INPUT (13) R R
Present_Value Unsigned 1 ~ 259 R R
Description CharacterString “AdaptorLink2_ErrorCode” O R
Device_Type CharacterString "Panasonic AC Gateway" O R
Status_Flags BACnetStatusFlags {FALSE, FALSE, FALSE, TRUE/FALSE} R R
Event_State BACnetEventState STATE_NORMAL (0) R R
Reliability BACnetReliability NO_FAULT_DETECTED (0) O R
Out_Of_Service BOOLEAN FALSE/TRUE R R
Number_Of_States Unsigned 259 R R
BACnetArray[32] of
State_Text Check Communication Status table below. O R
CharacterString
Time_Delay Unsigned - O -
Notification_Class Unsigned - O -
Alarm_Values List of Unsigned - O -
Fault_Values List of Unsigned - O -
Event_Enable BACnetEventTransitionBits - O -
Acked_Transitions BACnetEventTransitionBits - O -
Notify_Type BACnetNotifyType - O -
BACnetArray[N] of
Event_Time_Stamps - O -
BACnetTimeStamp
Profile_Name CharacterString - O -
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 21/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
Communication status table
Communication status interpretation is possible using the value in the following correspondence table.
Contents displayed Contents displayed Contents displayed
Pesent_Value Pesent_Value in State_Text Pesent_Value in State_Text
in State_Text
1 A01 44 C12 87 E23
2 A02 45 C13 88 E24
3 A03 46 C14 89 E25
4 A04 47 C15 90 E26
5 A05 48 C16 91 E27
6 A06 49 C17 92 E28
7 A07 50 C18 93 E29
8 A08 51 C19 94 E30
9 A09 52 C20 95 E31
10 A10 53 C21 96 ??
11 A11 54 C22 97 F01
12 A12 55 C23 98 F02
13 A13 56 C24 99 F03
14 A14 57 C25 100 F04
15 A15 58 C26 101 F05
16 A16 59 C27 102 F06
17 A17 60 C28 103 F07
18 A18 61 C29 104 F08
19 A19 62 C30 105 F09
20 A20 63 C31 106 F10
21 A21 64 ?? 107 F11
22 A22 65 E01 108 F12
23 A23 66 E02 109 F13
24 A24 67 E03 110 F14
25 A25 68 E04 111 F15
26 A26 69 E05 112 F16
27 A27 70 E06 113 F17
28 A28 71 E07 114 F18
29 A29 72 E08 115 F19
30 A30 73 E09 116 F20
31 A31 74 E10 117 F21
32 ?? 75 E11 118 F22
33 C01 76 E12 119 F23
34 C02 77 E13 120 F24
35 C03 78 E14 121 F25
36 C04 79 E15 122 F26
37 C05 80 E16 123 F27
38 C06 81 E17 124 F28
39 C07 82 E18 125 F29
40 C08 83 E19 126 F30
41 C09 84 E20 127 F31
42 C10 85 E21 128 ??
43 C11 86 E22 129 H01
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 22/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
Contents displayed Contents displayed Contents displayed
Pesent_Value Pesent_Value in State_Text Pesent_Value in State_Text
in State_Text
130 H02 174 J14 218 L26
131 H03 175 J15 219 L27
132 H04 176 J16 220 L28
133 H05 177 J17 221 L29
134 H06 178 J18 222 L30
135 H07 179 J19 223 L31
136 H08 180 J20 224 ??
137 H09 181 J21 225 P01
138 H10 182 J22 226 P02
139 H11 183 J23 227 P03
140 H12 184 J24 228 P04
141 H13 185 J25 229 P05
142 H14 186 J26 230 P06
143 H15 187 J27 231 P07
144 H16 188 J28 232 P08
145 H17 189 J29 233 P09
146 H18 190 J30 234 P10
147 H19 191 J31 235 P11
148 H20 192 ?? 236 P12
149 H21 193 L01 237 P13
150 H22 194 L02 238 P14
151 H23 195 L03 239 P15
152 H24 196 L04 240 P16
153 H25 197 L05 241 P17
154 H26 198 L06 242 P18
155 H27 199 L07 243 P19
156 H28 200 L08 244 P20
157 H29 201 L09 245 P21
158 H30 202 L10 246 P22
159 H31 203 L11 247 P23
160 ?? 204 L12 248 P24
161 J01 205 L13 249 P25
162 J02 206 L14 250 P26
163 J03 207 L15 251 P27
164 J04 208 L16 252 P28
165 J05 209 L17 253 P29
166 J06 210 L18 254 P30
167 J07 211 L19 255 P31
168 J08 212 L20 256 Comm_Error
169 J09 213 L21 257 Not_Exist
170 J10 214 L22 258 Scan
171 J11 215 L23 259 Normal
172 J12 216 L24
173 J13 217 L25
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 23/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
5.3.4 OnOff_All (Binary Output Object Type)
It allows control to turn the all indoor units On or Off at a time.
Property Identifier Property Datatype Value ASHRAE IBOX
Object_Identifier BACnetObjectIdentifier (Binary Output, 18) R R
Object_Name CharacterString "OnOff_All" R R
Object_Type BACnetObjectType BINARY_OUTPUT (4) R R
Present_Value BACnetBinaryPV INACTIVE (0) / ACTIVE (1) W W
Description CharacterString "OnOff_All " O R
Device_Type CharacterString "Panasonic AC Gateway” O R
Status_Flags BACnetStatusFlags {FALSE, FALSE, FALSE, TRUE/FALSE} R R
Event_State BACnetEventState STATE_NORMAL (0) R R
Reliability BACnetReliability NO_FAULT_DETECTED (0) O R
Out_Of_Service BOOLEAN TRUE/FALSE R R
Polarity BACnetPolarity NORMAL (0) R R
Inactive_Text CharacterString "Inactive" O R
Active_Text CharacterString “Active" O R
Change_Of_State_Time BACnetDatetime - O -
Change_Of_State_Count Unsigned - O -
Time_Of_State_Count_Reset BACnetDatetime - O -
Elapsed_Active_Time Unsigned - O -
Time_Of_Active_Time_Reset BACnetDatetime - O -
Minimum_Off_Time Unsigned32 - O -
Minimum_On_Time Unsigned32 - O -
Priority_Array BACnetPriorityArray - R R
Relinquish_Default BACnetBinaryPV - R R
Time_Delay Unsigned - O -
Notification_Class Unsigned - O -
Feedback_Value BACnetBinaryPV - O -
Event_Enable BACnetEventTransitionBits - O -
Acked_Transitions BACnetEventTransitionBits - O -
Notify_Type BACnetNotifyType - O -
BACnetArray[N] of
Event_Time_Stamps - O -
BACnetTimeStamp
Profile_Name CharacterString - O -
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 24/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
5.3.5 Mode_All (Multistate Output Object Type)
It allows control over the mode of all indoor units at a time.
Property Identifier Property Datatype Value ASHRAE IBOX
Object_Identifier BACnetObjectIdentifier (Multi-state Output, 19) R R
Object_Name CharacterString “Mode_All” R R
Object_Type BACnetObjectType MULTISTATE_OUTPUT (14) R R
Present_Value Unsigned 1~5 W W
Description CharacterString “Mode_All” O R
Device_Type CharacterString “Panasonic AC Gateway” O R
Status_Flags BACnetStatusFlags {FALSE, FALSE, FALSE, TRUE/FALSE} R R
Event_State BACnetEventState STATE_NORMAL (0) R R
Reliability BACnetReliability NO_FAULT_DETECTED (0) O R
Out_Of_Service BOOLEAN FALSE/TRUE R R
Number_Of_States Unsigned 5 R R
BACnetArray[2] of
State_Text Check Mode setting table below O R
CharacterString
Priority_Array BACnetPriorityArray - R R
Relinquish_Default Unsigned - R R
Time_Delay Unsigned - O -
Notification_Class Unsigned - O -
Feedback_Value Unsigned - O -
Event_Enable BACnetEventTransitionBits - O -
Acked_Transitions BACnetEventTransitionBits - O -
Notify_Type BACnetNotifyType - O -
BACnetArray[N] of
Event_Time_Stamps - O -
BACnetTimeStamp
Profile_Name CharacterString - O -
Mode setting table
Mode setting interpretation is possible using the value in the following correspondence table.
Pesent_Value Contents displayed in State_Text
1 Heat
2 Cool
3 Fan
4 Dry
5 Auto
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 25/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
5.3.6 SetPoint_All (Analog Output Object Type)
It allows control over the setpoint for all indoor units at a time.
Property Identifier Property Datatype Value ASHRAE IBOX
Object_Identifier BACnetObjectIdentifier (Analog Output, 20) R R
Object_Name CharacterString “System_Events” R R
Object_Type BACnetObjectType ANALOG_OUTPUT (1) R R
Present_Value REAL -15…60 (ºC) // 5 … 140 (ºF) (Default 0ºC) R R
Description CharacterString “SetPoint_All” O R
Device_Type CharacterString “Panasonic AC Gateway” O R
Status_Flags BACnetStatusFlags {FALSE, FALSE, FALSE, TRUE/FALSE} R R
Event_State BACnetEventState STATE_NORMAL (0) R R
Reliability BACnetReliability NO_FAULT_DETECTED (0) O R
Out_Of_Service BOOLEAN FALSE/TRUE R R
Update_Interval Unsigned 300 O R
Units BACnetEngineeringUnits Degrees Celsius (62) // Fahrenheit (64) R R
Min_Pres_Value REAL -15 (ºC) // 5 (ºF) O R
Max_Pres_Value REAL 60 (ºC) // 140 (ºF) O R
Resolution REAL 1 O R
COV_Increment REAL 1 O R
Time_Delay Unsigned - O -
Notification_Class Unsigned - O -
High_Limit REAL - O -
Low_Limit REAL - O -
Deadband REAL - O -
Limit_Enable BACnetLimitEnable - O -
Event_Enable BACnetEventTransitionBits - O -
-
Acked_Transitions BACnetEventTransitionBits O -
Notify_Type BACnetNotifyType - O -
BACnetArray[N] of
Event_Time_Stamps - O -
BACnetTimeStamp
Profile_Name CharacterString - O -
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 26/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
5.3.7 FanSpeed_All (Multistate Output Object Type)
It allows control over the all indoor units fan speed at a time.
Property Identifier Property Datatype Value ASHRAE IBOX
Object_Identifier BACnetObjectIdentifier (Multi-state Output, 21) R R
Object_Name CharacterString “FanSpeed_All” R R
Object_Type BACnetObjectType MULTISTATE_OUTPUT (14) R R
Present_Value Unsigned 1~4 W W
Description CharacterString “FanSpeed_All” O R
Device_Type CharacterString "Panasonic AC Gateway" O R
Status_Flags BACnetStatusFlags {FALSE, FALSE, FALSE, TRUE/FALSE} R R
Event_State BACnetEventState STATE_NORMAL (0) R R
Reliability BACnetReliability NO_FAULT_DETECTED (0) O R
Out_Of_Service BOOLEAN FALSE/TRUE R R
Number_Of_States Unsigned 4 R R
BACnetArray[4] of
State_Text Check Fan Speed setting table below O R
CharacterString
Priority_Array BACnetPriorityArray - R R
Relinquish_Default Unsigned - R R
Time_Delay Unsigned - O -
Notification_Class Unsigned - O -
Feedback_Value Unsigned - O -
Event_Enable BACnetEventTransitionBits - O -
Acked_Transitions BACnetEventTransitionBits - O -
Notify_Type BACnetNotifyType - O -
BACnetArray[N] of
Event_Time_Stamps - O -
BACnetTimeStamp
Profile_Name CharacterString - O -
Fan Speed setting table
Fan speed interpretation is possible using the value in the following correspondence table.
Pesent_Value Contents displayed in State_Text
1 Low
2 Medium
3 High
4 Auto
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 27/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134IntesisBox® BACnet/IP – Panasonic AC User Manual r2.1 eng
5.3.8 RemoteControl_Lock_All (Multistate Output Object Type)
It allows locking remote control activity from all indoor units at a time.
Property Identifier Property Datatype Value ASHRAE IBOX
Object_Identifier BACnetObjectIdentifier (Multi-state Output, 22) R R
Object_Name CharacterString “RemoteControl_Lock_All” R R
Object_Type BACnetObjectType MULTISTATE_OUTPUT (14) R R
Present_Value Unsigned 1 ~ 32 W W
Description CharacterString “RemoteControl_Lock_All” O R
Device_Type CharacterString "Panasonic AC Gateway" O R
Status_Flags BACnetStatusFlags {FALSE, FALSE, FALSE, TRUE/FALSE} R R
Event_State BACnetEventState STATE_NORMAL (0) R R
Reliability BACnetReliability NO_FAULT_DETECTED (0) O R
Out_Of_Service BOOLEAN FALSE/TRUE R R
Number_Of_States Unsigned 32 R R
BACnetArray[4] of
State_Text Check Remote Control Lock table below O R
CharacterString
Priority_Array BACnetPriorityArray - R R
Relinquish_Default Unsigned - R R
Time_Delay Unsigned - O -
Notification_Class Unsigned - O -
Feedback_Value Unsigned - O -
Event_Enable BACnetEventTransitionBits - O -
Acked_Transitions BACnetEventTransitionBits - O -
Notify_Type BACnetNotifyType - O -
BACnetArray[N] of
Event_Time_Stamps - O -
BACnetTimeStamp
Profile_Name CharacterString - O -
© Intesis Software S.L. - All rights reserved URL http://www.intesis.com 28/82
email info@intesis.com
IntesisBox is a registered trademark of Intesis Software SL
tel +34 938047134You can also read