MODELS SCFC-08-X-X-AECM-X-X X
This Surna fan coil is another addition to our full The unit uses an electronically commutated
line of purpose-built fan coil products providing (EC) fan motor and modulating valves can be
a wide range of choices for both ducted and integrated to allow for maximum output at
ductless applications for small to large commercial minimum energy consumption. The EC fan motor
indoor cannabis cultivation facilities. also provides extremely quiet operation.
This ceiling cassette ductless fan coil can be For simple maintenance, the air filter is easily
mounted in any comfort or process room where removable and washable and is made from self-
wall mounting or remote ducting are not desired extinguishing acrylic with an efficiency class Merv
taking up no extra floor or wall space. 2-4.
This unit is available in many different sizes.
These fan coils provide maximum flexibility and
application specific options, ensuring a precise
solution for your unique application.
FEATURES AND BENEFITS
Ductless Versatile Heating Options
Ductless application for chilled Available in multiple sizes and Surna’s cassette fan coils offer
water makes installation and can be mounted in any drop an electric heat kit or 4-pipe
cleaning simple. ceiling or ceiling recess. hot water re-heat options for
providing cooling and heating
options for any space.SPECIFICATIONS
Custom configurations and sizes may be available upon request
SCFC-08-V-X-AECM-X SCFC-08-V-X-AECM-X-EH SCFC-08-P-X-AECM-X
PHYSICAL 2-Pipe, Cooling Only 2-Pipe with Electric Heat 4-Pipe with Hot Water Reheat
Length 22-5/8 in (575 mm)
Width 22-5/8 in (575 mm)
Height 11-7/16 in (291 mm)
Weight 66.1 lbs (30 kg) 67.5 lbs (30.6 kg) 66.1 lbs (30 kg)
Water Inlet 3/4 in (19 mm) NPT
Water Outlet 3/4 in (19 mm) NPT
Condensate Drainage
Outside Diameter: 1 in (25 mm) / Inside Diameter: 13/16 in (21 mm)
Connection
Number of Fan Blowers Single
ELECTRICAL
Power Supply (V/Ph/Hz) 220/1/60
Power Input in Cooling Mode 47 W
Power Input in Heating Mode N/A 42W
Fan Motor Running Current
0.43 A
@220V
Min.Circuit Ampacity (MCA) 0.27 A 11.6 A 0.27 A
Max. Overcurrent Protection
15 A
(MOP)
Full Load Amps (FLA) 0.21 A 9.3 A 0.43 A
CHILLED WATER COIL PERFORMANCE
Total Airflow 476 CFM (808.7 m3/h)
Cooling Capacity 15342 BTU/Hr (4.5 kW) 12852 BTU/Hr (3.91 kW)
Sensible Cooling Capacity 10239 BTU/Hr (3 kW) 8794 BTU/Hr (2.81 kW)
Cooling Water Flow Rate 3 GPM (681.4 L/h) 2.5 GPM (567.8 L/h)
Cooling Water Pressure Drop 10.6 Ft/Head (31.8 kPa) 5.6 Ft/Head (16.8 kPa)
Heating Water Flow Rate N/A 0.7 GPM (159 L/h)
Heating Water Pressure Drop N/A 0.3 Ft/Head (0.9 kPa)
ELECTRIC HEAT PERFORMANCE
Max. Heating Capacity N/A 2 kW N/A
REHEAT COIL PERFORMANCE
Hydronic Heating Capacity
N/A 8794 BTU/hr (2.81 kW)
(EWT 1400F/60°C)
CERTIFICATIONS
ETL
Note:
a. Assumes entering water b. Data is based on fan running c. Data assumes specified GPM d. All dimensions are
temperature (EWT) of 450 F at maximum speed @ 220V approximate within 1/16 of an
(7.220 C) inch of those indicated
P 303.993.5271
August 2021
surna.com E info@surna.com All data subject to change without noticeISOSTREAM®
SURNA CASSETTE
FAN COIL
COOLING/OPTIONAL HEAT
MODELS SCFC-16-X-X-AECM-X-X X
This Surna fan coil is another addition to our full The unit uses an electronically commutated
line of purpose-built fan coil products providing (EC) fan motor and modulating valves can be
a wide range of choices for both ducted and integrated to allow for maximum output at
ductless applications for small to large commercial minimum energy consumption. The EC fan motor
indoor cannabis cultivation facilities. also provides extremely quiet operation.
This ceiling cassette ductless fan coil can be For simple maintenance, the air filter is easily
mounted in any comfort or process room where removable and washable and is made from self-
wall mounting or remote ducting are not desired extinguishing acrylic with an efficiency class Merv
taking up no extra floor or wall space. 2-4.
This unit is available in many different sizes.
These fan coils provide maximum flexibility and
application specific options, ensuring a precise
solution for your unique application.
FEATURES AND BENEFITS
Ductless Versatile Heating Options
Ductless application for chilled Available in multiple sizes and Surna’s cassette fan coils offer
water makes installation and can be mounted in any drop an electric heat kit or 4-pipe
cleaning simple. ceiling or ceiling recess. hot water re-heat options for
providing cooling and heating
options for any space.SPECIFICATIONS
Custom configurations and sizes may be available upon request
SCFC-16-V-X-AECM-X SCFC-16-V-X-AECM-X-EH SCFC-16-P-X-AECM-X
PHYSICAL 2-Pipe, Cooling Only 2-Pipe with Electric Heat 4-Pipe with Hot Water Reheat
Length 44-7/8 in (1140 mm)
Width 22-13/16 in (579 mm)
Height 11-7/16 in (291 mm)
Weight 115 lbs (52.2 kg) 120 lbs (54.4 kg) 115 lbs (52.2 kg)
Water Inlet 3/4 in (19 mm) NPT
Water Outlet 3/4 in (19 mm) NPT
Condensate Drainage
Outside Diameter: 1 in (25 mm) / Inside Diameter: 13/16 in (21 mm)
Connection
Number of Fan Blowers Twin
ELECTRICAL
Power Supply (V/Ph/Hz) 220/1/60
Power Input in Cooling Mode 89 W
Power Input in Heating Mode N/A 84 W
Fan Motor Running Current
0.81 A
@220V
Min.Circuit Ampacity (MCA) 0.51 A 17.6 A 0.51 A
Max. Overcurrent Protection
15 A 20 A 15 A
(MOP)
Full Load Amps (FLA) 0.4 A 14.04 0.4 A
CHILLED WATER COIL PERFORMANCE
Total Airflow 853 CFM (1449.3 m3/h)
Cooling Capacity 28497 BTU/Hr (8.4 kW) 16078 BTU/Hr (4.71 kW)
Sensible Cooling Capacity 19128 BTU/Hr (5.6 kW) 11280 BTU/Hr (3.31 kW)
Cooling Water Flow Rate 5.6 GPM (1271.9 L/h) 3.2 GPM (726.8 L/h)
Cooling Water Pressure Drop 12.8 Ft/Head (38.3 kPa) 4.5 Ft/Head (13.4 kPa)
Heating Water Flow Rate N/A 1.3 GPM (295.3 L/h)
Heating Water Pressure Drop N/A 0.5 Ft/Head (1.5 kPa)
ELECTRIC HEAT PERFORMANCE
Max. Heating Capacity N/A 3 kW N/A
REHEAT COIL PERFORMANCE
Hydronic Heating Capacity
N/A 25172 BTU/Hr (7.38 kW)
(EWT 1400F/60°C)
CERTIFICATIONS
ETL
Note:
a. Assumes entering water b. Data is based on fan running c. Data assumes specified GPM d. All dimensions are
temperature (EWT) of 450 F at maximum speed @ 220V approximate within 1/16 of an
(7.220 C) inch of those indicated
P 303.993.5271
August 2021
surna.com E info@surna.com All data subject to change without noticeISOSTREAM®
SURNA CASSETTE
FAN COIL
COOLING/OPTIONAL HEAT
MODELS SCFC-20-X-X-AECM-X-X X
This Surna fan coil is another addition to our full The unit uses an electronically commutated
line of purpose-built fan coil products providing (EC) fan motor and modulating valves can be
a wide range of choices for both ducted and integrated to allow for maximum output at
ductless applications for small to large commercial minimum energy consumption. The EC fan motor
indoor cannabis cultivation facilities. also provides extremely quiet operation.
This ceiling cassette ductless fan coil can be For simple maintenance, the air filter is easily
mounted in any comfort or process room where removable and washable and is made from self-
wall mounting or remote ducting are not desired extinguishing acrylic with an efficiency class Merv
taking up no extra floor or wall space. 2-4.
This unit is available in many different sizes.
These fan coils provide maximum flexibility and
application specific options, ensuring a precise
solution for your unique application.
FEATURES AND BENEFITS
Ductless Versatile Heating Options
Ductless application for chilled Available in multiple sizes and Surna’s cassette fan coils offer
water makes installation and can be mounted in any drop an electric heat kit or 4-pipe
cleaning simple. ceiling or ceiling recess. hot water re-heat options for
providing cooling and heating
options for any space.SPECIFICATIONS
Custom configurations and sizes may be available upon request
SCFC-20-V-X-AECM-X SCFC-20-V-X-AECM-X-EH SCFC-20-P-X-AECM-X
PHYSICAL 2-Pipe, Cooling Only 2-Pipe with Electric Heat 4-Pipe with Hot Water Reheat
Length 32-11/16 in (830 mm)
Width 32-11/16 in (830 mm)
Height 11-7/16 in (291 mm)
Weight 110 lbs (49.9 kg) 110.5 ibs (50.1 kg) 110 lbs (49.9 kg)
Water Inlet 3/4 in (19 mm) NPT
Water Outlet 3/4 in (19 mm) NPT
Condensate Drainage
Outside Diameter: 1 in (25 mm) / Inside Diameter: 13/16 in (21 mm)
Connection
Number of Fan Blowers Single
ELECTRICAL
Power Supply (V/Ph/Hz) 220/1/60
Power Input in Cooling Mode 224 W
Power Input in Heating Mode N/A 219 W
Fan Motor Running Current
2.04 A
@220V
Min.Circuit Ampacity (MCA) 1.27 A 2.4 A 1.27 A
Max. Overcurrent Protection
15 A 25 A 15 A
(MOP)
Full Load Amps (FLA) 1.02 A 19.2 A 2.04 A
CHILLED WATER COIL PERFORMANCE
Total Airflow 1300 CFM (2208.7 m3/h)
Cooling Capacity 32423 BTU/Hr (9.5 kW) 22318 BTU/Hr (6.54 kW)
Sensible Cooling Capacity 23166 BTU/Hr (6.8 kW) 15307 BTU/Hr (4.49kW)
Cooling Water Flow Rate 6.4 GPM (1453.6 L/h) 4.4 GPM (999.3 L/h)
Cooling Water Pressure Drop 8.8 Ft/Head (26.4 kPA) 6.8 Ft/Head (20.3 kPa)
Heating Water Flow Rate N/A 1.6 GPM (363.4 L/h)
Heating Water Pressure Drop N/A 0.7 Ft/Head (2.1 kPa)
ELECTRIC HEAT PERFORMANCE
Max. Heating Capacity N/A 4 kW N/A
REHEAT COIL PERFORMANCE
Hydronic Heating Capacity
N/A 31509 BTU/Hr (9.23 kW)
(EWT 1400F/60°C)
CERTIFICATIONS
ETL
Note:
a. Assumes entering water b. Data is based on fan running c. Data assumes specified GPM d. All dimensions are
temperature (EWT) of 450 F at maximum speed @ 220V approximate within 1/16 of an
(7.220 C) inch of those indicated